HP ProLiant Servers - Integrated Management Log Event Error Messages

Introduction to event list error messages

This document contains event list error messages recorded in the Integrated Management Log (IML), which can be viewed through different tools. The format of the list is different when viewed through different tools. An example of the format of an event as displayed on the Integrated Management Display (IMD) follows:

**001 of 010**

---caution---

03/19/2002

12:54 PM

FAN INSERTED

Main System

Location:

System Board

Fan ID: 03

**END OF EVENT**

WARNING: To avoid potential problems, ALWAYS read the warnings and cautionary information in the server documentation before removing, replacing, reseating, or modifying system components.

top

Event list error messages

NOTE: This listing of error messages provides information for multiple servers. Some information may not apply to the server you are troubleshooting. Refer to the server documentation for information on procedures, hardware options, software tools, and operating systems supported by the server.
NOTE: The error messages in this section may be worded slightly different than as displayed by the server.
A CPU Power Module
Error Message:
A CPU Power Module (System Board, Socket X)...
...A CPU Power Module (Slot X, Socket Y) Failed
Event type:
Power module failure
Action:
CAUTION: Only authorized technicians trained by HP should attempt to remove the system board. If you believe the system board requires replacement, contact HP Technical Support before proceeding.
Replace the power module. In the case of an embedded power module, replace the system board.
ASR Lockup Detected
Error Message:
ASR Lockup Detected: Cause
Event type:
System lockup
Action:
Examine the IML ("Integrated Management Log") to determine the cause of the lockup. For more information, refer to the HP ROM-Based Setup Utility User Guide on the server Documentation CD or the SmartStart Support and Documents website (http://www.hp.com/support/smartstart/documentation).
Automatic operating system shutdown #1
Error Message:
Automatic operating system shutdown initiated due to fan failure
Event type:
Fan failure
Action:
Replace the failed fan
Automatic operating system shutdown #2
Error Message:
Automatic Operating System Shutdown Initiated Due to Overheat Condition...
..Fatal Exception (Number X, Cause)
Event type:
Overheating condition
Action:
Check fans. Also, be sure the server is properly ventilated and the room temperature is set within the required range.
Blue Screen Trap
Error Message:
Blue Screen Trap: Cause [NT]...
...Kernel Panic: Cause [UNIX]
Abnormal Program Termination: Cause [NetWare]
Event type:
System lockup
Action:
Refer to the operating system documentation.
Corrected Memory Error
Error Message:
Corrected Memory Error Threshold Passed (Slot X, Memory Module Y)...
...Corrected Memory Error Threshold Passed (System Memory)
Corrected Memory Error Threshold Passed (Memory Module Unknown)
Event type:
Correctable error threshold exceeded
Action:
Continue normal operation, and then replace the memory module during the next scheduled maintenance to ensure reliable operation.
EISA Expansion Bus
Error Message:
EISA Expansion Bus Master Timeout (Slot X)...
...EISA Expansion Bus Slave Timeout
EISA Expansion Board Error (Slot X)
EISA Expansion Bus Arbitration Error
Event type:
Expansion bus error
Action:
Power down the server, and then replace the EISA board.
PCI Bus Error
Error Message:
PCI Bus Error (Slot X, Bus Y, Device Z, Function X)
Event type:
Expansion bus error
Action:
Replace the PCI board.
Processor Correctable Error
Error Message:
Processor Correctable Error Threshold Passed (Slot X, Socket Y)
Event type:
Correctable error threshold exceeded
Action:
Replace the processor.
Processor Uncorrectable Error
Error Message:
Processor Uncorrectable Internal Error (Slot X, Socket Y)
Event type:
Uncorrectable error
Action:
Replace the processor.
Real-Time Clock Battery
Error Message:
Real-Time Clock Battery Failing
Event type:
System configuration battery low
Action:
Replace the system configuration battery.
System AC Power Overload
Error Message:
System AC Power Overload (Power Supply X)
Event type:
Power supply overload
Action:
  1. Switch the voltage from 110 V to 220 V or add an additional power supply (if applicable to the system).
  2. If the problem persists, remove some of the installed options.
System AC Power Problem
Error Message:
System AC Power Problem (Power Supply X)
Event type:
AC voltage problem
Action:
Check for any power source problems.
System Fan Failure
Error Message:
System Fan Failure (Fan X, Location)
Event type:
Fan failure
Action:
Replace the fan.
System Fans Not Redundant
Error Message:
System Fans Not Redundant
Event type:
Fans not redundant
Action:
Add a fan or replace the failed fan.
System Overheating
Error Message:
System Overheating (Zone X, Location)
Event type:
Overheating condition
Action:
Check fans for correct operation.
System Power Supplies Not Redundant
Error Message:
System Power Supplies Not Redundant
Event type:
Power supply not redundant
Action:
Add a power supply or replace the failed power supply.
System Power Supply Failure
Error Message:
System Power Supply Failure (Power Supply X)
Event type:
Power supply failure
Action:
Replace the power supply.
Unrecoverable Host Bus Data Parity Error
Error Message:
Unrecoverable Host Bus Data Parity Error...
...Unrecoverable Host Bus Address Parity Error Event
Event type:
Host bus error
Action:
CAUTION: Only authorized technicians trained by HP should attempt to remove the system board. If you believe the system board requires replacement, contact HP Technical Support before proceeding.
Replace the board on which the processor is installed.
Uncorrectable Memory Error
Error Message:
Uncorrectable Memory Error (Slot X, Memory Module Y)...
...Uncorrectable Memory Error (System Memory)
Uncorrectable Memory Error (Memory Module Unknown)
Event type:
Uncorrectable error Action:
Action:
Replace the memory module. If the problem persists, replace the memory board.

top

HP BladeSystem p-Class infrastructure error codes

The server blade management modules and power management modules contain service ports that enable service personnel to gather fault information. To gather the fault information perform the following:
  1. Connect to the service port.
  2. Access the system diagnostics.
NOTE: For more information, refer to the HP BladeSystem Maintenance and Service Guide. Alll server blade documentation and manuals can be found on the HP Business Support Center (BSC) website. Click here to access the BSC Manuals for all HP server blade products .
Server blade management module error codes
LED error code:
Server blade LED error codes
Location:
Blade Enclosure Location
LED Code
Server Blade - Slot 1
1-1 or 1-2
Server Blade - Slot 2
2-1 or 2-2
Server Blade - Slot 3
3-1 or 3-2
Server Blade - Slot 4
4-1 or 4-2
Server Blade - Slot 5
5-1 or 5-2
Server Blade - Slot 6
6-1 or 6-2
Server Blade - Slot 7
7-1 or 7-2
Server Blade - Slot 8
8-1 or 8-2
Action:
Perform the following steps to resolve the problem. Stop when the problem is resolved.
  1. Reseat the server.
  2. Run system diagnostics. Replace any failed components.
  3. Replaced the server blade.
Refer to server documentation on the HP BSC website. Click here to access the BSC Manuals for all HP server blade products .
Server blade management module board error
LED error code:
Server blade management module board error codes LED code:
9-1, 9-2, 9-3, 9-4, 9-5, 9-6, 9-7, 9-8, 9-9, 9-10, 9-11, or 9-12
Location:
Server blade management module
Action:
Perform the following steps to resolve the problem. Stop when the problem is resolved.
  1. Press the server blade management module reset button.
  2. Replace the server blade management module.
Server blade management module signal backplane error
LED error code
Server blade management module signal backplane error codes
LED code: 10-1, 10-2, or 10-3
Location:
Server blade management backplane
Action:
Perform the following steps to resolve the problem. Stop when the problem is resolved. 1. Press the server blade management module reset button. 2. Replace the signal backplane. For more information, refer to the HP BladeSystem Maintenance and Service Guide on the HP website (http://www.hp.com/products/servers/proliant-bl/p-class/info).
Server blade management module power backplane A error
LED error codes
Server blade management module power backplane A error codes
LED code: 11-1, 11-2, 11-3, or 11-4
Location:
Server blade power backplane A
Action:
Perform the following steps to resolve the problem. Stop when the problem is resolved.
  1. Press the server blade management module reset button.
  2. Replace the power backplane.
For more information, refer to the HP BladeSystem Maintenance and Service Guide on the HP BSC website. Click here to access the BSC Manuals for all HP server blade products .
Server blade management module power backplane B error
LED error codes:
Server blade management module power backplane B error codes
LED code: 12-1, 12-2, 12-3, or 12-4
Location:
Server blade power backplane B
Action:
Perform the following steps to resolve the problem. Stop when the problem is resolved.
  1. Press the server blade management module reset button.
  2. Replace the power backplane.
For more information, refer to the HP BladeSystem Maintenance and Service Guide on the HP BSC website. Click here to access the BSC Manuals for all HP server blade products .
Interconnect A Error
LED error codes:
Interconnect A Error Code
LED code: 13-1, 13-2, 13-3, or 13-4
Location:
Interconnect device - side A
Action:
Perform the following steps to resolve the problem. Stop when the problem is resolved.
  1. Press the server blade management module reset button.
  2. Reseat the interconnect device.
  3. Replace the interconnect device.
For more information, refer to the HP BladeSystem Maintenance and Service Guide on the HP BSC website. Click here to access the BSC Manuals for all HP server blade products .
Interconnect B Error
LED error codes:
Interconnect B Error Code
LED code: 14-1, 14-2, 14-3, or 14-4
Location:
Interconnect device - side B
Action:
Perform the following steps to resolve the problem. Stop when the problem is resolved.
  1. Press the server blade management module reset button.
  2. Reseat the interconnect device.
  3. Replace the interconnect device.
For more information, refer to the HP BladeSystem Maintenance and Service Guide on the HP BSC website. Click here to access the BSC Manuals for all HP server blade products .
Interconnect Module A (10-Connector) Error
LED error codes:
Interconnect Module A (10-Connector) Error Code
LED code: 15-1 or 15-2
Location:
Interconnect module - side A (10-connector)
Action:
Perform the following steps to resolve the problem. Stop when the problem is resolved.
  1. Press the server blade management module reset button.
  2. Reseat the interconnect module.
  3. Replace the interconnect module.
For more information, refer to the HP BladeSystem Maintenance and Service Guide on the HP BSC website. Click here to access the BSC Manuals for all HP server blade products .
Interconnect Module A (6-Connector) Error
LED error codes:
Interconnect Module A (6-Connector) Error Code
LED code: 17-1 or 17-2
Location:
Interconnect module - side A (6-connector)
Action:
Perform the following steps to resolve the problem. Stop when the problem is resolved.
  1. Press the server blade management module reset button.
  2. Reseat the interconnect module.
  3. Replace the interconnect module.
For more information, refer to the HP BladeSystem Maintenance and Service Guide on the HP BSC website. Click here to access the BSC Manuals for all HP server blade products .
Interconnect Module B (10-Connector) Error
LED error codes:
Interconnect Module B (10-Connector) Error Code
LED code: 16-1 or 16-2
Location:
Interconnect module - side B (10-connector)
Action:
Perform the following steps to resolve the problem. Stop when the problem is resolved.
  1. Press the server blade management module reset button.
  2. Reseat the interconnect module.
  3. Replace the interconnect module.
For more information, refer to the HP BladeSystem Maintenance and Service Guide on the HP BSC website. Click here to access the BSC Manuals for all HP server blade products .
Interconnect Module B (6-Connector) Error
LED error codes:
Interconnect Module B (6-Connector) Error Code
LED code: 18-1 or 18-2
Location:
Interconnect module - side B (6-connector)
Action:
Perform the following steps to resolve the problem. Stop when the problem is resolved.
  1. Press the server blade management module reset button.
  2. Reseat the interconnect module.
  3. Replace the interconnect module.
For more information, refer to the HP BladeSystem Maintenance and Service Guide on the HP BSC website. Click here to access the BSC Manuals for all HP server blade products .
Unknown server blade management module error
LED error codes:
Unknown server blade management module error code
LED code: 19-1
Location:
Unknown
Action:
Perform the following steps to resolve the problem. Stop when the problem is resolved.
  1. Press the server blade management module reset button.
  2. Replace the server blade management module.
Power management module error codes
LED error codes:
Power supply error codes
Location:
Blade Enclosure Location
LED Code
Power Supply - Slot 1
1-1 or 1-2
Power Supply - Slot 2
2-1 or 2-2
Power Supply - Slot 3
3-1 or 3-2
Power Supply - Slot 4
4-1 or 4-2
Power Supply - Slot 5
5-1 or 5-2
Power Supply - Slot 6
6-1 or 6-2
Action:
Perform the following steps to resolve the problem. Stop when the problem is resolved.
  1. Reseat the power supply.
  2. Reseat the power management module.
  3. Replace the power supply.
For more information, refer to the HP BladeSystem Maintenance and Service Guide on the HP BSC website. Click here to access the BSC Manuals for all HP server blade products .

Power management module board error
LED error codes:
Power management module board error codes
LED code: 7-1, 7-2, 7-3, 7-4, 7-5, 7-6, 7-7, 7-8, 7-9, 7-10, 7-11, 7-12, or 7-13
Location:
Power management board
Action:
Perform the following steps to resolve the problem. Stop when the problem is resolved.
  1. Reseat the power management module.
  2. Replace the power management module.

Location:

Power management module backplane error
LED error codes:
Power management module backplane error codes
LED code: 8-1, 8-2, 8-3, 8-4, 8-5, 8-6, 8-7, or 8-8
Location:
Power management backplane
Action:
Perform the following steps to resolve the problem. Stop when the problem is resolved.
  1. Press the power management module reset button.
  2. Replace the power management module.
Unknown power management module error
LED error codes:
Unknown power management module error code
LED code: 19-1
Location:
Unknown
Action:
Perform the following steps to resolve the problem. Stop when the problem is resolved.
  1. Press the power management module reset button.
  2. Replace the power management module.

top